Technical specifications for IC660BBS103
Brand GE Fanuc
Series Genius module I/O
Part number IC660BBS103
Module Type Discrete I/O module
Nooooo. Circuit number eight (8) circuits
Input voltage range, AC 93-132 volts AC
Input voltage range, DC 105-132 VDC
Nominal input voltage, AC 115 volts AC
Nominal input voltage, DC 125 V DC
Input filter 10 to 100 ms, in 10 ms increments
Open delay AC: 0.5Hz + 1ms, DC: 1ms
Input diagnosis open circuit, overheat, I/O power loss
Output diagnosis of short circuit, overload, no-load, overheat, I/O power loss
Output current AC: 2A RMS, DC: 2A resistor (1A inductor)
Fuse internal electronic short-circuit trip. 100ms (AC), 10ms (DC) long travel

GE Fanuc IC660BBS103 is a Genius I/O module. The hardware is an intelligent module with eight (8) circuits that can be used as input and output channels. It can operate at AC or DC voltages such as 115 VAC and 125VDC.
The IC660BBS103 measures 8.83 inches (22.44 cm) x 3.34 inches (8.48 cm) x 3.91 inches (9.93 cm) (height x width x depth) and weighs 4 pounds (1.8 kg). It comes with status LED indicators, such as unit normal and I/O enabled, as well as separate leds for each module circuit. It has a block-to-block isolation rating of 1500V, a maximum heat dissipation of 16.8W when all inputs are turned on, and a maximum of 45.6W when all outputs of each circuit are energized at 2 amps. It operates at 93-132VAC, 47-63 Hz, and 105-132VDC. It has a power voltage drop time of 1 cycle when operating at AC voltage and 10 milliseconds when operating at DC voltage.
For input operations, the processing time is 2 ms for AC operations and 0.8 ms for DC operations. Both processing times are directly affected by the configured filter times of 10 to 100 milliseconds in increments of 10 milliseconds. The input circuit detects Open Wire, Overtemperature, and I/O power loss.
For output operation, the output circuit provides 2A AC operation and 2A resistance and 1A induced current when operating at DC voltage. The on-off delay of the module is 0.5Hz + 1ms (AC operation) and 1ms (DC operation). The output circuit is equipped with internal electronic short circuit trip, AC operation is 100 ms, DC operation is 10 ms. In addition, the output circuit has an internal diagnostic function for short circuit, overload, no-load, overheating and I/O power loss.