Technical specifications for IC660TBA103
Brand GE Fanuc
Series Genius I-O
Part number IC660TBA103
Block type 6 thermocouple compatible inputs, three isolation groups of 2 each
Rated voltage 115 V AC / 125 V DC
Supply voltage 93 to 132 volts AC, 9 watts / 105 to 145 volts DC, 9 watts
Power supply voltage drop time 1 cycle (AC) / 10 ms (DC)
Frequency/Ripple 47 to 63 Hz / 10% Max ripple
Heat dissipation (Max.) 9 watts
Block to block isolation 1500 volts for 1 minute
Group to group 300 volts
Dimensions (H x W x D) 224 x 88 x 100 mm (8.8 x 3.5 x 3.9 in)
Weight 1.8 kg (4 lb)
Operating temperature 0 to 60 degrees Celsius (32 to 140 degrees Fahrenheit)
Storage temperature -40 to 100 degrees Celsius (-40 to 212 degrees Fahrenheit)


The GENIUS terminal assembly of the IC660TBA103 is part of the thermocouple block and is used to control temperature input. This module model consists of 6 inputs divided into 3 identical isolated sets. The terminal is equipped with an LED indicator and has a maximum heat dissipation of 9 watts. The IC660TBA103 terminal assembly has an inter-block isolation voltage of 1500 volts and an inter-group isolation voltage of 300 volts. The input update time for all channels of this component is 2 to 3 seconds, and various diagnostic functions are included. The functions of the thermocouple block are configurable and they include baud rate, fault reporting, low alarm, high alarm, BSM controller and offset value.

The IC660TBA103 terminal assembly can be configured to respond differently to different errors. If the user chooses to disable fault detection for the terminal through the "channel active" function, the inactive channel of the terminal will not display the fault. The terminals can also be adjusted to avoid fault reports for specific block circuits so that fault reports are not sent to the CPU. However, even if the fault detection function is turned off, the connected computer will handle the fault. The IC660TBA103 terminal assembly has a power supply voltage range of 93 to 132 volts AC, and also supports DC operation in the 105 to 145 volts DC range. The device has an exit time of 47 to 63 Hertz and a maximum ripple of 10%. The terminal assembly can measure the input voltage in the range of -25.0 mV to +150 mV.