Technical specifications for IC660TBA105
Brand GE Fanuc
Series Genius I-O
Part number IC660TBA105
Block type 6 current source outputs
Rated voltage 115 V AC / 125 V DC
Supply voltage 93 to 132 volts AC / 105 to 145 volts DC
Maximum current 250 mA (AC) / 140 MA (DC)
Frequency/Ripple 47 to 63 Hz / 10% Max ripple
Power supply voltage drop time 1 cycle (AC) / 10 ms (DC)
Heat dissipation (Max.) 12 watts
Block to block isolation 1500 volts for 1 minute
Dimensions (H x W x D) 224 x 88 x 100 mm (8.8 x 3.5 x 3.9 in)
Weight 1.8 kg (4 lb)
Operating temperature 0 to 60 degrees Celsius (32 to 140 degrees Fahrenheit)
Storage temperature -40 to 100 degrees Celsius (-40 to 212 degrees Fahrenheit)

GE Fanuc terminal assemblies, known as IC660TBA105 terminal assemblies, are used in industrial control systems that consist of high-quality components that must operate at a high level. The terminal assembly is part of the current source analog output module, and its output has different functions as well as crucial diagnostic functions. The terminal assembly has an output accuracy of 0.15% at a temperature level of 25 degrees Celsius, and its fault reporting function can be turned on or off for a specific circuit. The IC660TBA105 terminal is a GE Genius I/O component that is compatible with the Genius bus controller series. It can also connect to PCIM and QBIM modules. The configuration of the block is performed via a handheld monitor.
The IC660TBA105 terminal assembly withstands vibrations of 5 to 10 Hz and a displacement of 5.08 mm (0.2 in). The relative humidity level in the terminal operating environment should be between 5% and 95%. The device can be stored in a temperature range of -40 to 100 degrees Celsius or -40 to 212 degrees Fahrenheit. Operating temperatures range from 0 to 60 degrees Celsius or 32 to 140 degrees Fahrenheit. The IC660TBA105 terminal assembly is rated for 115 volts AC and 125 volts DC. Ac operation requires a power supply with a maximum current of 250 mA and DC operation with a maximum current of 140 mA. The device has a minimum power voltage drop time of 10 milliseconds and a maximum ripple of 10%. The IC660TBA105 terminal assembly has an output signal accuracy of 0.15% for full scale readings and an update frequency of 25 ms.